1. The instrument is designed as a high-precision test equipment to detect grid waveform distortion occurrence, the harmonic content , voltage fluctuations and flicker and phase imbalance of power quality problems; It also includes electrical parameters testing, vector analysis functions.
2. It can accurately measure a variety of electrical parameters, such as voltage, current, active power, reactive power, phase angle, power factor, frequency, etc.
3. It can display the vector diagram of the measured voltage and current , by analyzing which users can judge if the metering device wiring is correct or not.
4. Current is measured by using the clamp transformers. You can easily and securely do the measurement, because of the use of clamp current transformers, without connecting the current loop. Depending on the user's measurement range, you can be equipped with different range of clamps.
5. Measurement and analysis of the AC power quality from the utility grid to client can be done easily, its measurement and analysis: frequency deviation, voltage deviation, voltage fluctuations, flicker, three-phase voltage unbalance factor and harmonic.
6. It can display single-phase voltage, current waveform and can display three-phase voltage and current waveform at the same time.
1. Input characteristics
Voltage measuring range: 10~660V.
Current measurement range
Clamp transformers (four types): 5A / 25A (standard)
100A / 500A (optional)
400A / 2000A (optional)
1000A/5000A (optional)
Phase angle measuring range: 0 ~ 359.99 °.
Frequency measurement range: 45 ~ 65Hz.
Voltage channels: three-channel (UA、UB、UC).
Current channels: three-channel (IA、IB、IC).
Maximum harmonic analysis times: 63 times.
Maximum continuous storage period in 1 minute interval: 18 months.
2. Accuracy
Measurement of electrical parameters section:
Voltage: ± 0.2%
Frequency: ± 0.01Hz
Current, power: ± 0.5%
Phase: ± 0.2 °
Power quality section:
Fundamental voltage tolerance: ≤0.5% F.S.
Fundamental current tolerance: ≤1% F.S.
Phase between fundamental voltage and current measurement error: ≤0.2 °
Percentage of harmonic voltage measurement error: ≤0.1%
Percentage of harmonic current measurement error: ≤0.2%
Three phase voltage unbalance error: ≤0.2%
Voltage deviation error: ≤0.2%
Voltage fluctuation error: ≤0.2%
3. Working temperature: -10 ℃ ~ + 40 ℃
4. Charging Power: 220V AC, 45Hz-65Hz frequency
5. Host Power: ≤3VA
6. Battery maximum working time: ≤10 hours
7. Insulation:
1) The insulation resistance between the voltage, current input terminal and the housing ≤100MΩ.
2) Withstand 1.5KV (valid value) with power frequency on operating power input and the shell, which lasts one minute.
8. Size: 258mm × 158mm × 58mm
9. Weight: 1.8Kg