Product Parameter
Working power supply: AC220V±10%, 50Hz/110V±10%, 60Hz
The device outputs 0 to 180Vrms and 5Arms (equivalent peak 20A).
Equivalent excitation voltage: 2500V
The excitation measurement accuracy is ≤0.5%
The secondary resistance range/accuracy is 0.1 to 300Ω / ≤0.5%
Secondary load range/accuracy: 5VA to 1000VA / ≤0.5%
The power factor range is 0.1 to 1
The angular difference measurement range/accuracy is 0-360°/ ±0.05°
The difference measurement accuracy is 0.05%
The CT ratio range/accuracy is ≤25000A/5A (5000A/1A) /0.2%
The PT ratio range/accuracy is ≤500KV /0.2%
Operating environment temperature: -20℃ to 50℃, humidity: ≤90%
Altitude: ≤1000m
Product specification and dimensions: 340mm × 270mm × 165mm, weight: ≤6Kg
Current transformer CT
• Volt-ampere characteristic curve (calculating inflection point values)
• Automatically provide inflection point values
•Automatically provide error curves of 5% and 10%
• Ratio measurement, polarity determination
•Secodary direct resistance measurement at any temperature
• Rated load measurement
• Secondary actual load measurement
• Power factor measurement
• Automatic demagnetization
• Angular difference measurement
• Differential measurement
• Accuracy Limit Coefficient (ALF)
• Instrument Security factor (FS)
Voltage transformer PT
• Volt-ampere characteristic curve (calculating inflection point values)
• Automatically provide inflection point values
• Ratio measurement
•Polarity judgment
•Secondary direct resistance measurement at any temperature
• Secondary actual load measurement
• Power factor measurement
• Automatic demagnetization
• Angular difference measurement
• Differential measurement
Product Feature And Application
1. Adopt advanced frequency conversion principles.
2. It features comprehensive detection and itemized detection functions, making on-site use more flexible.
3. Quickly detect the actual secondary load and power factor of the transformer.
4. Automatically detect 5% and 10% error curves.
5. Automatically provide inflection point values and Kalf.
6. It is equipped with a built-in micro fast printer, allowing for direct on-site printing of test results.
7. It adopts a TFT color LCD touch screen display, making operation simpler and more convenient.
8. The built-in memory can store 10,000 sets of test data, which will not be lost after power failure.
9. When used in conjunction with a USB flash drive, it can achieve unlimited storage.
10. Configure the data analysis software, which can generate detection reports through a PC.
Accessory
Number | Name | Amount |
1 | main unit | one |
2 | instruction manual | one |
3 | test report | one |
4 | power cord | one |
5 | secondary side test leads (equipped with alligator clips) | one |
6 | grounding wire (with alligator clip) | three |
7 | insurance tubes | five |
8 | printing paper | two |