+86 13720145047lunagangrui@gmail.com
    Follow Us
Products
Home >>Products >>CT PT Analyzer
CT PT Analyzer

Volt-ampere characteristics Analyzer

  • It is used for the automatic testing of the characteristics of protection type, metering type, GIS bushing, zero sequence and other transformers. Support the detection of parameters such as CT and PT (protection, metrology, measurement, GIS casing, zero-sequence CT)
Chat Now
Contact Us+86 13720145047

Details

Product Parameter

             

Working power supply: AC220V±10%, 50Hz/110V±10%, 60Hz

The device outputs 0 to 180Vrms and 5Arms (equivalent peak 20A).

Equivalent excitation voltage: 2500V

The excitation measurement accuracy is ≤0.5%

The secondary resistance range/accuracy is 0.1 to 300Ω / ≤0.5%

Secondary load range/accuracy: 5VA to 1000VA / ≤0.5%

The power factor range is 0.1 to 1

The angular difference measurement range/accuracy is 0-360°/ ±0.05°

The difference measurement accuracy is 0.05%

The CT ratio range/accuracy is ≤25000A/5A (5000A/1A) /0.2%

The PT ratio range/accuracy is ≤500KV /0.2%

Operating environment temperature: -20℃ to 50℃, humidity: ≤90%

Altitude: ≤1000m

Product specification and dimensions: 340mm × 270mm × 165mm, weight: ≤6Kg

Current transformer CT

• Volt-ampere characteristic curve (calculating inflection point values)

• Automatically provide inflection point values

•Automatically provide error curves of 5% and 10%

• Ratio measurement, polarity determination

•Secodary direct resistance measurement at any temperature

• Rated load measurement

• Secondary actual load measurement

• Power factor measurement

• Automatic demagnetization

• Angular difference measurement

• Differential measurement

• Accuracy Limit Coefficient (ALF)

• Instrument Security factor (FS)

Voltage transformer PT

• Volt-ampere characteristic curve (calculating inflection point values)

• Automatically provide inflection point values

• Ratio measurement

•Polarity judgment

•Secondary direct resistance measurement at any temperature

• Secondary actual load measurement

• Power factor measurement

• Automatic demagnetization

• Angular difference measurement

• Differential measurement

 

Product Feature And Application

1. Adopt advanced frequency conversion principles.

2. It features comprehensive detection and itemized detection functions, making on-site use more flexible.

3. Quickly detect the actual secondary load and power factor of the transformer.

4. Automatically detect 5% and 10% error curves.

5. Automatically provide inflection point values and Kalf.

6. It is equipped with a built-in micro fast printer, allowing for direct on-site printing of test results.

7. It adopts a TFT color LCD touch screen display, making operation simpler and more convenient.

8. The built-in memory can store 10,000 sets of test data, which will not be lost after power failure.

9. When used in conjunction with a USB flash drive, it can achieve unlimited storage.

10. Configure the data analysis software, which can generate detection reports through a PC.

Accessory

Number

Name

Amount

1

main unit

one

2

 instruction manual

one

3

test report

one

4

power cord

one

5

secondary side test leads (equipped with alligator clips)

one

6

grounding wire (with alligator clip)

three

7

insurance tubes

five

8

printing paper

two


WhatsApp
Hotline

Service hotline

+86 13720145047